TECHNICAL DATA |
|||||||||
Model |
SGUV Mark 2 |
||||||||
Part No. |
SPFM-100-F |
SPFM-150-F |
|||||||
Size (mm) |
100 |
150 |
|||||||
Orifice Plate |
Stainless Steel mounted in a 38mm thick, red polyester coated steel carrier ring |
||||||||
Measuring Tube |
Borosilicate glass with 100mm fused-in ceramic scale |
||||||||
Float |
Stainless Steel |
||||||||
Accuracy |
±5% at various test flows specified by LPCB |
||||||||
‘O’ Seals |
Nitrile |
||||||||
Indicator Housing |
Die-cast aluminium with white polyester coating, black bezel and perspex window |
||||||||
Impulse Pipe |
Bright nickel plated copper with plated brass connections |
||||||||
Filter Unit |
316 Stainless Steel element with 1.5mm perforations, TPX tube, plated brass connections and nitrile ‘O’ seals |
||||||||
Flow Range |
150-12,500 dm3/min |
||||||||
Pressure Limitation |
12 bar g @ 20°C |
||||||||
Pressure Test |
30 bar hydraulic |
||||||||
Pressure Drop |
At max flow rate 65% of the orifice pressure loss of 354”WG is recovered |
||||||||
Standard Flow Ranges |
|||||||||
Flanged |
Grooved |
Nominal Pipe Size (mm) |
Flow Ranges 3 |
Test Flows 3 |
Test Flows Accuracy 3 |
||||
LPCB |
PLATON |
LPCB |
PLATON |
||||||
088a/5 |
F1/5 |
088a/10 |
F1/10 |
50 |
150 - 750 |
500 800 |
± 25 ± 40 |
||
088a/6 |
F1/6 |
088a/11 |
F1/11 |
80 |
300 - 2300 |
1300 1500 |
± 65 ± 75 |
||
088a/7 |
F1/7 |
088a/12 |
F1/12 |
100 |
500 - 3500 |
2200 2500 3500 |
± 110 ± 125 ± 175 |
||
088a/8 |
F1/8 |
088a/13 |
F1/13 |
150 |
900 - 8200 |
4500 5000 |
± 225 ± 250 |
||
088a/9 |
F1/9 |
088a/14 |
F1/14 |
200 |
2500 - 12500 |
7000 9000 |
± 350 ± 450 |